Style 2000IC

Flexible Graphite, Wire Reinforced

Description and Applications

Style 2000IC is manufactured from high purity flexible graphite that is expanded and formed into a weave-able yarn and then braided in a unique construction with wire reinforcement. The finished product retains all the inherent benefits of flexible graphite; while the wire reinforcement provides greater mechanical strength. Style 2000IC packing is particularly suited for use in high temperature, high pressure steam service. In addition, it can also handle most chemicals, acids and alkalis. This style is excellent for use in steam turbines, high temperature motor-actuated valves and for high pressure/high temperature valve applications in general.

Service Limits

Temperature ºF (ºC)
Minimum -464 (-240)
Maximum 842 (450)
Steam 1202 (650)
Pressure psi (bar)
Static 5800 (400)
pH
Minimum 0
Maximum 14

Approximate Yields (+/-10%)

Size Ft/Lb 116.3 54 30.2 19.9 13.9 10.1 8 6.3 5.2 3.6 2.7 2.2
Inch 1/8 3/16 1/4 5/16 3/8 7/16 1/2 9/16 5/8 3/4 7/8 1
Package 1 Lb (0.5kg) 2 Lbs (1kg) 5 Lbs (2kg) 10 Lbs (5kg)
Other spools are availabel on request

Approximate Yields (+/-10%)

Tests realized by Yarmouth Research and Technology Maine – USA

Fire Test

Objective
Qualify packing Style 2000IC for fire resistance when applied to valves subjected to direct flame.

Test Procedure
API STANDARD 589 – SECOND EDITION

Test Parameters
Exposure time to fire – 40 minutes;
Temperature in the valve body up to 679ºC;
Allowable Leakage, pressures of the test and measurements done according to table below.

Conclusion
Packing Style 2000IC has successfully completed the test easily reaching the requirements of this standard.

Approximate Yields (+/-10%)

Parameters Leaks(ml/min) Pressure
Measured Allowable (psiq)
During the 2 minutes pretest hydrostatic 0.0 0 537
During firing and cooling 0.0 60 567
During the low pressure test after firing 0.0 3 50
After the closing and opening operation 0.4 60 537

Fugitive Emission Test

Objective
To qualify packing style 2000IC for fugitive emissions in valves when subjected to thermal and mechanical cycles.

Leak detection method
“EPA method 21”.

Test Procedure
ARCO Fugitive Emission Test Specification.

Test Parameters
3 thermal cycles at room temperature and at 177ºC;
Leakage measurements are performed before and after each thermal cycle and at each 100 cycles of the shaft;
Test pressure: 645 psig (45 Kgf/cm2);
Test Fluid: Foxboro OVA128 (99% methane);
Maximum allowable leakage: 100 PPMv (if the leak allowed exceeds 100 PPMv, the sobreposta must be adjusted).

Conclusion
Packing 2000IC has successfully completed the test with 5 adjustments during the 3,500 cycles while maintaining leakage under 100 PPMv.